As a general contractor I work with many different architects. Some architects call for sealant to be placed along the bottom edge of a metal coping and the masonry wall. Others don't. Is this sealant necessary or is it simply overkill?
-
Whether or not sealant is needed depends on how far the metal coping laps over the top edge of the masonry wall. If the metal coping laps less than 4 inches, sealant may be needed to prevent water from blowing up under the metal coping. If the lap is 4 inches or greater, the sealant probably is not necessary.